ST420F-L9 combined electrical fire monitoring detector
1) Device Overview
ST420F-L9series of combined electrical fire monitoring detector devices are designed690Vthe followingTT,TNsystem design, through the distribution circuit of the residual current and temperature of electrical fire hazard parameters to implement monitoring and management, so as to prevent the occurrence of electrical fires, is the ideal choice for chemical enterprise electrical fire prevention monitoring. The device is composed of protection main body (including display), residual current transformer, temperature sensor and other parts. The protection main body of the device is installed on the cabinet panel, and the other parts are installed in the cabinet.
2) Device Model

Note:
1) Standard1RoadModbus-RTUCommunications and1relay output;
2) has9residual current measurement and1road temperature measurement function.
3) technical parameters
Analog Input Loop
|
Rated residual currentI△n |
1A |
|
frequencyF |
50Hz |
Measurement range and accuracy
|
Name |
|
accuracy |
|
residual currentI△ |
50 ~ 1000mA |
≤± 1% |
|
temperature |
0°C~ 200°C |
≤± 5% |
protection action accuracy
|
residual current |
300 ~ 1000mA |
≤1mA |
|
temperature |
45-140°C |
≤1°C |
|
protection delay time |
0.1~ 60.0s |
≤0.1s |
Auxiliary power supply
|
power supply voltage (both AC and DC) |
AC 85~264V,DC 90~300V |
|
power consumption(is normal./protection) |
≤3W / 5W |
relay output (standard 1 way)
|
R(open and close) |
AC250V 5A,DC30V 5A |
communication function
|
Modbus-RTUStatute |
1channel, RS485 interface, terminal access |
Alarm function
|
Alarm mode |
Sound and light alarm |
|
Alarm Record |
8alarm records |
|
audio device |
70~115dB |
work environment
|
working temperature |
-10~ +40 ℃ |
|
storage temperature |
-20~ +70 ℃ |
|
relative humidity |
5~ 95% (no condensation or ice inside) |
|
altitude |
<2500m |
|
IPlevel |
IP20 |
4) Contour Installation
Device body
dimensions: 76.7mm × 112.3mm × 57.8mm (length and widthhigh).

Installation Method
device is the standard in the cabinet.35mmrail installation.

5) Terminal Arrangement

6) Terminal Definition

7) Typical Wiring

-
System and software products
-
Communication equipment set
-
DC integrated equipment
-
Communication switch electrical components
-
DC switchgear components
-
ꄶ Mechanical and Electrical Equipment Control Box
-
Medium-pressure protection device
-
ꄶ Circuit breaker accessories
-
ꄶ Low-voltage protection device
-
ꄶ Electrical fire protection device
-
ꄶ Multifunctional instrument
-
ꄶ Intelligent integrated device
-
Communication device
-
Current transformer