ST400S Series Microcomputer Line Protection Device
ST400SSeries Microcomputer Line Protection Device
1)Device Overview
ST400Sseries microcomputer line protection device is a protection of the main body and display module split device, suitable for rated frequency 50/60Hz, rated voltage below 1kV into the line, feeder and PT circuit applications. The device is composed of protection main body, display module, special current transformer, residual current transformer, external expansion module and other parts. The device display module is installed on the cabinet panel, and the rest is installed in the cabinet.
2)Device Model

Note:
1)display module with WiFi function;
2) See "2.3 Current Transformer" in this chapter for current transformer ";
3)EIO function has 1 channel of 4 ~ 20mA analog output, 1 channel of temperature input, 4 channels of DI input, 2 channels of DO output and 1 channel of zero sequence voltage input; (The sub-model EIO1 has 1 channel of 4 ~ 20mA analog output and 1 channel of temperature input);
4)ETM 6-way PT1000 input.
3)technical parameters
Analog Input Loop
|
transformer rated current In |
1A, 5A, 25A, 100A, 160A, 400A |
|
Rated voltage Un |
AC100V, AC400V, AC690V |
|
frequency F |
50/60Hz |
|
Rated residual current I △n |
1A |
|
current circuit |
2incontinuous operation; 10In is allowed to operate for 10s; 40Inis allowed to run for 1s |
|
voltage circuit |
1.2UnContinuous operation; 1.4Un is allowed to operate for 10s |
|
power consumption |
No current, voltage <1VA/phase |
Measurement range and accuracy
|
Name |
|
accuracy |
|
current I |
0.1~1.2 In |
≤±0.5%In |
|
voltage U |
0.1~1.2 Un |
≤±0.5%Un |
|
active power P electrical degree EP |
|Cosφ|≥0.707 U/Un=(50~ 120)% I /In=(50~ 120)% |
≤ ± 1% |
|
power factor COS |
|Cosφ|≥0.707 |
≤ ± 1% |
|
Residual current I △ |
0.5~1.2 I△n |
≤±1%I△n |
|
current harmonics |
Ih/In=(5~ 50)% I /In=(50~ 120)% |
≤±1%In |
|
voltage harmonics |
Uh/Un=(5~ 50)% U/Un=(50~ 120)% |
≤±1%Un |
|
analog output |
4~ 20mA |
≤ ± 0.5% |
|
temperature |
0~ 200 ℃ |
≤ ± 1 ℃ |
protection action accuracy
|
Current/voltage fixed value |
≤ ± 3% fixed value |
|
|
Delay time T |
T<4S |
≤ ± 35ms |
|
T≥ 4s |
≤ ± 1% fixed value |
|
|
return coefficient |
Overprotection |
<0.95 percentfixed value |
|
undershoot protection |
>1.05 percentfixed value |
|
|
residual current |
50~ 1000mA |
≤ ± 1mA |
|
temperature |
45~ 140 ℃ |
≤ ± 1 ℃ |
Auxiliary power supply
|
power supply voltage (both AC and DC) |
AC 85~264V,DC 90~300V |
|
power consumption (normal/protected) |
≤ 3W / 5W |
|
surge current |
≤ 20A |
|
working power supply |
2S |
switch input (standard 11, optional 4)
|
Isolation Method |
optical isolation |
|
Power supply mode |
ST400S*FBuilt-in power current source ST400S*Mexternal AC220V ST400S * H1external DC110V ST400S * H2external DC220V |
|
response time |
<50ms |
relay output (standard 6, optional 2)
|
R1, R2, R3, R4 |
AC250V 10A,DC30V 10A |
|
R5, R6 |
AC250V 7A,DC30V 7A |
analog (4 ~ 20mA) transmission output
|
transmission parameters |
three-phase current, three-phase voltage, residual current, active power |
|
Load resistance |
≤ 750Ω |
communication function
|
Modbus-RTUStatute |
1/2channel, RS485 interface, terminal access |
|
Modbus-TCPStatute |
2channel, Ethernet interface, RJ45 access |
|
PROFINETStatute |
2channel, Ethernet interface, RJ45 access |
|
PROFIBUS-DPV1Statute |
1/2way, PROFIBUS interface, DB9 access |
work environment
|
working temperature |
-25~ +55 ℃ |
|
storage temperature |
-25~ +70 ℃ |
|
relative humidity |
5~ 95% (no condensation or ice inside) |
|
altitude |
<3000m |
|
IPlevel |
≥ IP20 (Panel ≥ IP40) |
4)Contour Installation
Device Body
dimensions: 75.0mm × 100.0mm × 115.0mm (length and widthhigh).

the width (100mm) and height (115mm) of the main body of the product and the expansion module are the same, but the length is different, as shown in the following figure:

Display Module ST522S
are: 103.0mm × 64.5mm × 45.9mm (length, width and depth), and the opening dimensions of the panel are: 91.5mm × 54.5mm (length, width).

Installation Method
device protection is standard 35mm guide rail installation or fixed installation in the cabinet, and the guide rail installation method of the external expansion module can only use the guide rail shown in the left view of the main body.

device is to install the buckle to fix the opening of the panel, install the four buckles along the grooves at the four corners of the device, and push them forward tightly, so that the front end is squeezed on the cabinet body, so that the device is installed.

5)Terminal Arrangement

6)Terminal Definition




-
System and software products
-
Communication equipment set
-
DC integrated equipment
-
Communication switch electrical components
-
DC switchgear components
-
ꄶ Mechanical and Electrical Equipment Control Box
-
Medium-pressure protection device
-
ꄶ Circuit breaker accessories
-
ꄶ Low-voltage protection device
-
ꄶ Electrical fire protection device
-
ꄶ Multifunctional instrument
-
ꄶ Intelligent integrated device
-
Communication device
-
Current transformer