ST570LF series motor protection controller
1)Device Overview
ST570LFseries combined electrical fire monitoring detector device isa protection of the main body and display module integrated device, suitable for rated frequency 50/60Hz, rated voltage below 1kV motor circuit applications.At the same time, the device is also aimed690Vthe followingTT,TNsystem design, through the distribution circuit of the residual current and temperature of electrical fire hazard parameters to implement monitoring and management, so as to prevent the occurrence of electrical fires, is the ideal choice for chemical enterprise electrical fire prevention monitoring. The device consists of a protective body (including display),special current transformer,consists of residual current transformer, temperature sensor and other parts. The main body of the device protection is installed on the cabinet panel, and the rest is installed in the cabinet.
2)Device Model

Note:
1) Standard 1 channel Modbus-RTU communication and WiFi function;
2)AC660V/690V circuit application shall be specified when ordering;
3) See "2.3 Current Transformers" in this chapter for current transformers ".
3)technical parameters
Analog Input Loop
|
transformer rated current In |
1A, 5A, 25A, 100A, 160A, 400A |
|
Rated voltage Un |
AC380V/400V |
|
frequency F |
50/60Hz |
|
Rated residual current I △n |
1A |
|
current circuit |
2incontinuous operation; 10In is allowed to operate for 10s; 40Inis allowed to run for 1s |
|
voltage circuit |
1.2UnContinuous operation; 1.4Un is allowed to operate for 10s |
|
power consumption |
No current, voltage <1VA/phase |
Measurement range and accuracy
|
Name |
|
accuracy |
|
current I |
0.5~1.2 In |
≤±0.5%In or 0.0025A |
|
voltage U |
0.5~1.2 Un |
≤±0.5%Un |
|
active power P |
|Cosφ|≥0.707 U/Un=(50~ 120)% I /In=(50~ 120)% |
≤ ± 0.5% |
|
Electrical EP/EQ |
≤±0.2kWh/kvarh |
|
|
frequency F |
45to 65Hz |
≤ ± 0.05Hz |
|
power factor COS |
|Cosφ|≥0.707 |
≤ ± 0.5% |
|
Residual current I △ |
50~ 1000mA |
≤± 1% |
|
current harmonics |
Ih/In=(5~ 50)% I /In=(50~ 120)% |
≤±1%In |
|
voltage harmonics |
Uh/Un=(5~ 50)% U/Un=(50~ 120)% |
≤±1%Un |
|
analog output |
4~ 20mA |
≤ ± 0.5% |
|
temperature |
0~ 140 ℃ |
≤ ± 1 ℃ |
protection action accuracy
|
Current/voltage fixed value |
≤ ± 3% fixed value |
|
|
heat accumulation |
≤ ± 5% |
|
|
Thermal overload time |
≤ ± 5% or ± 50ms |
|
|
tEtime |
≤ ± 3% or ± 50ms |
|
|
Time-limited protection delay time T |
T<4S |
≤ ± 20ms |
|
T≥ 4s |
≤ ± 1% fixed value or ± 20ms |
|
|
return coefficient |
Overprotection |
<0.95 percentfixed value |
|
underprotection |
>1.05 percentfixed value |
|
|
residual current |
300~ 1000mA |
≤ ± 1mA |
|
temperature |
45~ 140 ℃ |
≤ ± 1 ℃ |
Auxiliary power supply
|
power supply voltage (both AC and DC) |
AC 85~264V,DC 90~300V |
|
power consumption (normal/protected) |
≤ 3W / 5W |
|
surge current |
≤ 20A |
|
working power supply |
2S |
switch input (standard 8)
|
isolation method |
optical isolation |
|
Power supply mode |
Built-in DC24V |
|
response time |
≤ 50ms |
relay output (standard 4 way)
|
R1, R2, R3 |
AC250V 10A,DC30V 10A |
|
R5 |
AC250V 5A,DC30V 5A |
analog (4 ~ 20mA) transmission output
|
transmission parameters |
three-phase current, three-phase voltage, leakage current, active power |
|
Load resistance |
≤ 750Ω |
communication function
|
Modbus-RTUStatute |
1/2channel, RS485 interface, terminal access |
|
Modbus-TCPStatute |
2channel, Ethernet interface, RJ45 access |
|
PROFIBUS-DPV0Statute |
1way, PROFIBUS interface, DB9 access |
Alarm function
|
Alarm mode |
Audible and visual alarm |
|
Alarm Record |
16alarm records |
|
audio device |
70~115dB |
work environment
|
working temperature |
-25~ 60 ℃ |
|
storage temperature |
-25~ +70 ℃ |
|
relative humidity |
5~ 95% (no condensation or ice inside) |
|
altitude |
<3000m |
|
IPlevel |
≥ IP20 (Panel ≥ IP40) |
4)Contour Installation
Device Body
are: 103.0mm × 64.5mm × 122.0mm (length, width and depth), and the opening dimensions of the panel are: 87.5mm × 51.0mm (length and width).



Installation Method
device is to install the buckle to fix the opening of the panel, install the four buckles along the grooves at the four corners of the device, and push them forward tightly, so that the front end is squeezed on the cabinet body, so that the device is installed.

5)Terminal Arrangement

6)Terminal Definition

7) Typical Wiring

-
System and software products
-
Communication equipment set
-
DC integrated equipment
-
Communication switch electrical components
-
DC switchgear components
-
ꄶ Mechanical and Electrical Equipment Control Box
-
Medium-pressure protection device
-
ꄶ Circuit breaker accessories
-
ꄶ Low-voltage protection device
-
ꄶ Electrical fire protection device
-
ꄶ Multifunctional instrument
-
ꄶ Intelligent integrated device
-
Communication device
-
Current transformer